Order No.
|
6EP1 434-2BA10
|
Input
|
3-phase AC
|
Rated voltage Uin rated
|
400-500 V AC
Wide-range input
|
Voltage range
|
340 ... 550 V
|
Overvoltage strength
|
2.3 x Uin rated, 1.3 ms
|
Mains buffering at Iout rated
|
> 6 ms/typ. 14 ms at Uin = 400 V
|
Rated line frequency, rated line frequency range
|
50/60 Hz; 47 ... 63 Hz
|
Rated current Iinrated
|
0.7-0.5 A
|
Switch-on current limitation (+25 °C)
|
< 36 A
|
I2 t
|
< 0.9 A2s
|
Built-in incoming fuse
|
None
|
Required protection in the mains supply conductor
|
3-pole coupled miniature circuit breaker 6 ... 16 A Characteristic C or circuit breaker 3RV2011-1DA10, setting 3 A or 3RV2711-1DD10 (UL 489)
|
Output
|
Controlled, isolated DC voltage
|
Rated voltage Uout rated
|
24 V DC
|
Total tolerance
|
±3 %
|
|
Approx. ±0.5 %
|
|
Approx. ±1%
|
Residual ripple
|
< 150 mVpp
|
Spikes (bandwidth approx. 20 MHz)
|
< 240 mVpp
|
Adjustment range
|
24 ... 28.0 V (max. 240 W)
|
Status indicator
|
24 V OK = green LED
|
Signaling
|
Relay contact (NO contact, rating 60 V DC/0.3 A) for 24 V OK
|
On/Off behavior
|
No overshoot of Uout (soft start)
|
Startup delay /
voltage rise
|
< 1.5 s/typ. 30 ms
|
Rated current Iout rated
|
10 A
|
Current range
|
|
|
0 ... 10 A (up to +70°C)
|
|
12 A (to +45 °C)
|
Dynamic overcurrent on
|
|
-
Power-up on short-circuit
|
Approx. 16 A for 100 ms
|
-
Short-circuit during operation
|
Approx. 16 A for 100 ms
|
Parallel switching for enhanced performance
|
Yes, 2 units
|
Efficiency
|
|
Efficiency at Uout rated, Iout rated
|
Approx. 91 %
|
Power loss at Uout rated, Iout rated
|
Approx. 24 W
|
Closed-loop control
|
|
Dynamic line smoothing (Uin rated ±15%)
|
< 3 % Uout
|
Dynamic load smoothing (Iout: 50/100/50 %)
|
Typ. ±3% Uout
|
Load step settling time
|
|
|
< 10 ms (typ. 2 ms)
|
|
< 10 ms (typ. 2 ms)
|
Protection and monitoring
|
|
Output overvoltage protection
|
Yes, according to EN 60950
|
Current limitation
|
Typ. 11 A, overload capability 150%Iout rated up to 5 s/min
|
Short-circuit protection
|
Electronic shutdown, automatic restart
|
Sustained short-circuit current rms value
|
Approx. 3.2 A
|
Overload/short-circuit indicator
|
-
|
Safety
|
|
Primary/secondary isolation
|
Yes, safety extra low output voltage Uout according to EN 60950-1 and EN 50178
|
Safety class
|
Class I
|
Leakage current
|
< 3.5 mA (typ. 1 mA)
|
Safety test
|
Yes; CB scheme
|
CE marking
|
Yes
|
UL/cUL (CSA) approval
|
cULus-listed (UL 508, CSA 22.2 No. 107.1), File E197259
|
Protection against explosion
|
ATEX EX II 3G Ex nAC IIC T4
|
Degree of protection (EN 60529)
|
IP20
|
EMC
|
|
Emitted interference
|
EN 55022 Class B
|
Supply harmonics limitation
|
EN 61000-3-2
|
Noise immunity
|
EN 61000-6-2
|
Operating data
|
|
Ambient temperature range
|
0 ... +70 °C with natural convection
|
Transport and storage temperature range
|
-40 ... +85°C
|
Humidity class
|
Climate class 3K3 according to
EN 60721, no condensation
|
Mechanics
|
|
Connections
|
|
-
Supply input L1, L2, L3 PE
|
1 screw-type terminal each for 0.2 ... 4 mm2 solid/finely stranded
|
|
2 screw-type terminals for 0.2 ... 4 mm2
|
|
2 screw-type terminals for 0.2 ... 4 mm2
|
|
2 screw-type terminals for 0.14 ... 1.5 mm2
|
Dimensions (W x H x D) in mm
|
90 x 145 x 150
|
Weight, approx.
|
1.6 kg
|
Mounting
|
Can be snapped onto standard mounting rail EN 60715 35x7.5/15
|
Accessories
|
Device labeling plates (3RT1900-1SB20)
|