TYPE
|
Portable transformer winding resistance meter
|
PHYSICAL SPECIFICATIONS
|
21” W x 17” H x 9” D (53 cm x 43 cm x 24 cm); Weight: 35 lbs (15.8Kg)
|
OPERATING VOLTAGE
|
100 – 240 Vac, 50/60 Hz
|
RESISTANCE READING RANGE
|
1 micro-ohm to 500 Ohms
|
ACCURACY
|
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count
20 – 999 milliohms: ±1% reading, ±1 count
1 -2000 Ohms: ±1.5% reading, ±1 count
|
TEST CURRENT
|
1-40A in 1A increments
|
TEST VOLTAGE
|
60 Vdc charging, 18V DC max during measurement
|
INPUT CHANNELS
|
4 input channels for measuring resistance
|
DISPLAY
|
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
|
PRINTER
|
Built-in 2.5" wide thermal printer
|
INTERNAL DATA STORAGE
|
256 static test records (each can contain up to 111 readings) and 120 dynamic test records
|
EXTERNAL DATA STORAGE
|
Up to 999 test records on external USB Flash drive.
|
COMPUTER INTERFACES
|
RS-232C, USB, Bluetooth
|
SAFETY
|
Designed to meet UL 61010A-1 and Can/CSA C22.2 No 1010.1092 standards
|
ENVIRONMENT
|
Operating: -10?C to 50?C (15?F to +122?F)
Storage: (-30?C to 70?C (-22?F to +158?F)
|
HUMIDITY (MAX)
|
90% RH @ 40? C (104? F) non-condensing
|
ALTITUDE (MAX)
|
2000m (6562 ft) to full safety specifications
|
CABLES
|
Four 50-foot test cables, one LTC control cable, one ground cable, one power cord, one USB cable
|
OPTIONS
|
Shipping Case
|
WARRANTY
|
One year on parts and labor
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|